3KE4530-0EA
SW. DISCON. W. ROT. OP. MECH. 690V/1000A

From SIEMENS

SWITCH DISCONNECTOR 3-POLE I=1000A, U=690V, DOOR COUPLING OPERATING MECHANISM 8UC6 BLACK KNOB, SHAFT 12 X 12MM
Model
Product brand nameSENTRON
Product designationSwitch Disconnector 3KE
versioncomplete version with door coupling rotary operating mechanism, lockable, with black handle
Design typeFor mounting and installation
Design of the operating mechanismmanual operating mechanism
Design of the load switch / Strip formNo
Type of the driving mechanism / motor driveNo
Number of poles3
Type of voltageAC/DC
Insulation voltage / rated value1 000 V
Protection class
Protection class IPIP00
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole60 W
Electricity
Continuous current / rated value1 000 A
Let-through current / I2 t / maximum permissible / in utilization category / AC-22 B / at 400 V19 000 000 A²·s
Main circuit
Number of poles / for main current circuit3
Operating voltage
at AC / at 50/60 Hz / rated value690 V
at DC / rated value440 V
Rated current Ie / maximum / in utilization category
AC-21 A / at 400 V1 000 A
AC-21 A / at 500 V1 000 A
AC-21 B / at 400 V1 000 A
AC-21 B / at 500 V1 000 A
AC-22 A / at 400 V800 A
AC-22 A / at 500 V800 A
AC-22 B / at 400 V800 A
AC-22 B / at 500 V800 A
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Number of NC contacts / for auxiliary contacts0
Number of NO contacts / for auxiliary contacts0
Product feature / interlockYes
Product extension
Auxiliary switchYes
optional
— motor driveNo
— Voltage triggerNo
— interlockYes
Short circuit
Maximum short-circuit current breaking capacity (Icu) / at 400 V / rated value40 000 A
Conditional rated short-circuit current
400V40 000 A
500V40 000 A
in utilization category / AC-21 A / at 400 V40 000 A
in utilization category / AC-21 A / at 500 V40 000 A
in utilization category / AC-21 B / at 400 V40 000 A
in utilization category / AC-21 B / at 500 V40 000 A
in utilization category / AC-22 A / at 400 V40 000 A
in utilization category / AC-22 A / at 500 V40 000 A
in utilization category / AC-22 B / at 400 V40 000 A
in utilization category / AC-22 B / at 500 V40 000 A
Connections
Connectable conductor cross-section
for main contacts
— stranded / maximum480 mm²
Type of connection, main circuitFlat-type screw terminal; M12
Type of electrical connection
for main current circuitflat connector
Mechanical Design
Height290 mm
Width209 mm
Depth521 mm
Type of mountingfixed mounted
Mounting typefloor mounting
Mounting type
front mounting with 4-hole attachmentNo
front mounting with central attachmentNo
rail mountingNo
Environmental conditions
Ambient temperature
during operation / minimum-20 °C
during operation / maximum55 °C
during storage / minimum-50 °C
during storage / maximum80 °C

External links