| SIRIUS Compact load feeder DOL starter for IO-Link 690 V 24 V DC 0.1...0.4 A IP20 Connection main circuit: Screw terminal Connection control circuit: screw terminal |
Product brand name | SIRIUS |
Product designation | Compact starter for IO-Link |
Design of the product | direct starter |
Product type designation | 3RA64 |
General technical data |
Product function | |
Control circuit interface to parallel wiring | No |
Product extension | |
Auxiliary switch | Yes |
Insulation voltage | |
rated value | 690 V |
Degree of pollution | 3 |
Surge voltage resistance rated value | 6 000 V |
Protection class IP | IP20 |
Shock resistance | a=60 m/s2 (6g) with 10 ms per 3 shocks in all axes |
Mechanical service life (switching cycles) | |
of the main contacts typical | 10 000 000 |
of auxiliary contacts typical | 10 000 000 |
of the signaling contacts typical | 10 000 000 |
Electrical endurance (switching cycles) of auxiliary contacts | |
at DC-13 at 6 A at 24 V typical | 30 000 |
at AC-15 at 6 A at 230 V typical | 200 000 |
Type of assignment | continous operation according to IEC 60947-6-2 |
Reference code acc. to DIN EN 81346-2 | Q |
Reference code acc. to DIN EN 61346-2 | Q |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Ambient temperature | |
during operation | -20 ... +60 °C |
during storage | -55 ... +80 °C |
during transport | -55 ... +80 °C |
Relative humidity during operation | 10 ... 90 % |
Main circuit |
Number of poles for main current circuit | 3 |
Adjustable pick-up value current of the current-dependent overload release | 0.1 ... 0.4 A |
Formula for making capacity limit current | 120 x Ie |
Formula for interruption capacity limit current | 100 x Ie |
Mechanical power output for 4-pole AC motor | |
at 400 V rated value | 0.09 kW |
at 500 V rated value | 0.12 kW |
at 690 V rated value | 0.18 kW |
Operating voltage | |
at AC-3 rated value maximum | 690 V |
Operating current | |
at AC at 400 V rated value | 0.4 A |
at AC-43 | |
— at 400 V rated value | 0.3 A |
— at 500 V rated value | 0.32 A |
— at 690 V rated value | 0.35 A |
Operating power | |
at AC-3 | |
— at 400 V rated value | 90 W |
at AC-43 | |
— at 400 V rated value | 90 W |
— at 500 V rated value | 120 W |
— at 690 V rated value | 180 W |
No-load switching frequency | 3 600 1/h |
Operating frequency | |
at AC-41 acc. to IEC 60947-6-2 maximum | 750 1/h |
at AC-43 acc. to IEC 60947-6-2 maximum | 250 1/h |
Control circuit/ Control |
Type of voltage | DC |
Holding power | |
at DC maximum | 2.9 W |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | 0 |
Number of NO contacts for auxiliary contacts | 0 |
Number of CO contacts | |
of the current-dependent overload release for signaling contact | 0 |
Operating current of auxiliary contacts at AC-12 maximum | 10 A |
Operating current of auxiliary contacts at DC-13 | |
at 250 V | 0.27 A |
Protective and monitoring functions |
Trip class | CLASS 10 and 20 adjustable |
Operational short-circuit current breaking capacity (Ics) | |
at 400 V | 53 kA |
at 500 V rated value | 3 kA |
at 690 V rated value | 3 kA |
UL/CSA ratings |
Full-load current (FLA) for three-phase AC motor | |
at 480 V rated value | 0.4 A |
at 600 V rated value | 0.4 A |
Short-circuit protection |
Product function Short circuit protection | Yes |
Design of short-circuit protection | electromagnetic |
Design of the fuse link | |
for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
Installation/ mounting/ dimensions |
Mounting position | any |
recommended | vertical, on horizontal standard mounting rail |
Mounting type | screw and snap-on mounting |
Height | 170 mm |
Width | 45 mm |
Depth | 165 mm |
Connections/Terminals |
Product function | |
removable terminal for main circuit | Yes |
removable terminal for auxiliary and control circuit | Yes |
Type of electrical connection | |
for main current circuit | screw-type terminals |
for auxiliary and control current circuit | screw-type terminals |
Type of connectable conductor cross-sections | |
for main contacts | |
— solid | 2x (1.5 ... 6 mm²), 1x 10 mm² |
— finely stranded with core end processing | 2x (1.5 ... 6 mm²) |
at AWG conductors for main contacts | 2x (16 ... 10), 1x 8 |
Type of connectable conductor cross-sections | |
for auxiliary contacts | |
— solid | 0.5 ... 4 mm², 2x (0.5 ... 2.5 mm²) |
— finely stranded with core end processing | 0.5 ... 2.5 mm², 2x (0.5 ... 1.5 mm²) |
at AWG conductors for auxiliary contacts | 2x (20 ... 14) |
Safety related data |
B10 value | |
with high demand rate acc. to SN 31920 | 3 000 000 |
Proportion of dangerous failures | |
with high demand rate acc. to SN 31920 | 50 % |
Communication/ Protocol |
Product function Bus communication | Yes |
Protocol is supported | |
IO-Link protocol | Yes |
Product function Control circuit interface with IO link | Yes |
IO-Link transfer rate | COM2 (38,4 kBaud) |
Point-to-point cycle time between master and IO-Link device minimum | 2.5 ms |
Type of voltage supply via input/output link master | No |
Amount of data | |
of the address area of the inputs with cyclical transfer total | 2 byte |
of the address area of the outputs with cyclical transfer total | 2 byte |
Electromagnetic compatibility |
Conducted interference | |
due to burst acc. to IEC 61000-4-4 | 4 kV main circuits, 2 kV auxiliary circuits, 2 kV IO-Link, 2 kV limit switches, 2 kV line hand-held device |
due to conductor-earth surge acc. to IEC 61000-4-5 | 4 kV main circuits, 0.5 kV auxiliary voltage with upstream overvoltage protection |
due to conductor-conductor surge acc. to IEC 61000-4-5 | 2 kV main circuits, 0.5 kV auxiliary voltage with upstream overvoltage protection |
due to high-frequency radiation acc. to IEC 61000-4-6 | 0.15-80Mhz at 10V |
Field-bound parasitic coupling acc. to IEC 61000-4-3 | 80 ... 3000 MHz at 10V/m |
Electrostatic discharge acc. to IEC 61000-4-2 | 8 kV |
Conducted HF-interference emissions acc. to CISPR11 | 150 kHz ... 30 MHz Class A |
Field-bound HF-interference emission acc. to CISPR11 | 30 ... 1000 MHz Class A |
Supply voltage |
Supply voltage required Auxiliary voltage | Yes |
Display |
Display version | |
as status display of the input/output link device | green/red dual LED |