3RG9002-0DA00
ACTUATOR SENSOR INTERFACE F90

From SIEMENS

AS-Interface module F90, digital 4 DI/4 DQ, IP20 4 x inputs for 3-wire sensor 4 x output, 2 A, 24 V DC maximal 6 A for all outputs Connection via screw terminals Width 90 mm
General technical data:
Design of the productF90 module - I/O modules for operation in the control cabinet, IP20
Type4 inputs / 4 outputs
Design of the slave typestandard slave
I/O configuration7
ID/ID2 code0/F
Type of electrical connection of the inputs and outputsscrew-type terminals
AS interface total current input maxmA270
operating voltage according to AS-Interface spezificationV26.5 ... 31.6
Addressingpossible using integrated addressing socket
Watchdogbuilt-in
Note 1An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III.
Sensor supply:
Type of voltage supply for power supplyusing AS-Interface
Property of the sensor supply Short-circuit and overload resistantYes
Ampacity of the sensor supply for all inputs at ambient temperature 40 °CmA200
Inputs:
Number of digital inputs4
Type of connection2- and 3-conductor PNP transistor
Input circuitPNP transistor
Type of voltage of the input voltagesDC
Input current at digital input
for signal <1> minimummA5
with signal <0> maximummA1.5
Inputs
switching level High minV10
sensor supply using AS-Interfaceshort-circuit and overload resistant
connection sensors2- and 3-conductor technology
Outputs:
Number of digital outputs4
Type of voltage of output voltagesDC
Outputs external power supply 24 V DCusing screw-type terminals
Output current at digital output for signal <1> Rated valueA2
Type of switching outputsolid state
Outputs total current of all outputsA6
Property of the output Short-circuit proofYes
Outputs
short-ciruit protectionbuilt-in
induction protectionbuilt-in
Status display
display of I/Osyellow LEDs
display of AS-Interface/diagnosticsgreen/red dual LED
Assignment of data bits
D0IN1/OUT1
D1IN2/OUT2
D2IN3/OUT3
D3IN4/OUT4
Ambient conditions:
Ambient temperature
during operation°C-25 ... +70
during storage°C-40 ... +85
Protection class IPIP20
Mechanical data:
Widthmm90
Heightmm75
Depthmm37
Mounting type35 mm standard rail mounting

External links