6ES7131-6BF00-0AA0
ET 200SP, DI 8x24VDC Basic

From SIEMENS

*** Spare part *** SIMATIC ET 200SP, digital input module, DI 8x 24 V DC Basic, packing quantity: 1 unit, suitable for BU type A0, color code CC01, module diagnostics
General information
Product type designationDI 8x24 VDC BA
Firmware versionV1.0
FW update possibleYes
usable BaseUnitsBU type A0
Color code for module-specific color identification plateCC01
Product function
I&M dataYes; I&M0 to I&M3
Engineering with
STEP 7 TIA Portal configurable/integrated as of versionV13 SP1
STEP 7 configurable/integrated as of versionV5.5 SP3 / -
PROFIBUS as of GSD version/GSD revisionGSD Revision 5
PROFINET as of GSD version/GSD revisionGSDML V2.3
Operating mode
DIYes
CounterNo
OversamplingNo
MSINo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)8 mA; without sensor supply
Current consumption, max.70 mA; All channels are supplied from the encoder supply
Encoder supply
Number of outputs8
Output voltage encoder supply, min.19.2 V
Short-circuit protectionNo
24 V encoder supply
24 VYes
Short-circuit protectionYes
Output current, max.700 mA
Power loss
Power loss, typ.1.6 W; 24 V, 8 inputs supplied via encoder supply
Address area
Address space per module
Address space per module, max.1 byte
Inputs1 byte
Hardware configuration
Selection of BaseUnit for connection variants
1-wire connectionBU type A0
2-wire connectionBU type A0
3-wire connectionBU type A0 with AUX terminals
4-wire connectionBU type A0 + external terminals
Digital inputs
Number of digital inputs8
Source/sink inputP-reading
Input characteristic curve in accordance with IEC 61131, type 1Yes
Input characteristic curve in accordance with IEC 61131, type 2Yes
Input characteristic curve in accordance with IEC 61131, type 3Yes
Pulse extensionNo
Input voltage
Rated value (DC)24 V
for signal "0"-30 to +5V
for signal "1"+11 to +30V
Input current
for signal "1", typ.6.8 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableYes; None / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 µs to 500 µs, depending on line length)
for interrupt inputs
— parameterizableNo
for technological functions
— parameterizableNo
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.2 mA
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Monitoring the supply voltageYes
— parameterizableYes
Monitoring of encoder power supplyNo
Wire-breakNo
Short-circuitNo
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; Green LED
for channel diagnosticsNo
for module diagnosticsYes; green/red DIAG LED
Potential separation
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsNo
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.28 g
last modified:03/28/2019