| *** Spare part *** SIMATIC ET 200SP, digital input module, DI 16X 24 V DC Standard, suitable for BU type A0, color code CC00, module diagnostics |
General information |
Product type designation | DI 16x24 VDC ST |
Firmware version | V1.1 |
FW update possible | Yes |
usable BaseUnits | BU type A0 |
Color code for module-specific color identification plate | CC00 |
Product function |
I&M data | Yes; I&M0 to I&M3 |
Engineering with |
STEP 7 TIA Portal configurable/integrated as of version | V13 SP1 |
STEP 7 configurable/integrated as of version | V5.5 / - |
PCS 7 configurable/integrated as of version | V8.1 SP1 |
PROFIBUS as of GSD version/GSD revision | GSD Revision 5 |
PROFINET as of GSD version/GSD revision | GSDML V2.3 |
Operating mode |
DI | Yes |
Counter | No |
Oversampling | No |
MSI | No |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
Current consumption, max. | 90 mA |
Encoder supply |
Short-circuit protection | No |
24 V encoder supply |
24 V | No |
Short-circuit protection | No |
Power loss |
Power loss, typ. | 1.7 W |
Address area |
Address space per module |
Address space per module, max. | 2 byte; + 2 bytes for QI information |
Hardware configuration |
Automatic encoding | |
Mechanical coding element | Yes |
Selection of BaseUnit for connection variants |
1-wire connection | BU type A0 |
2-wire connection | BU type A0 + external terminals |
3-wire connection | BU type A0 + external terminals |
4-wire connection | BU type A0 + external terminals |
Digital inputs |
Number of digital inputs | 16 |
Source/sink input | P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input characteristic curve in accordance with IEC 61131, type 2 | No |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Pulse extension | No |
Input voltage |
Rated value (DC) | 24 V |
for signal "0" | -30 to +5V |
for signal "1" | +11 to +30V |
Input current |
for signal "1", typ. | 2.5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable | Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) |
— at "0" to "1", min. | 0.05 ms |
— at "0" to "1", max. | 20 ms |
— at "1" to "0", min. | 0.05 ms |
— at "1" to "0", max. | 20 ms |
for interrupt inputs |
— parameterizable | No |
for technological functions |
— parameterizable | No |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Alarms |
Diagnostic alarm | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Monitoring the supply voltage | Yes |
— parameterizable | Yes |
Monitoring of encoder power supply | No |
Wire-break | Yes; Module-by-module, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm |
Short-circuit | No |
Group error | Yes |
Diagnostics indication LED |
Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Channel status display | Yes; Green LED |
for channel diagnostics | No |
for module diagnostics | Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
between the channels | No |
between the channels and backplane bus | Yes |
between the channels and the power supply of the electronics | No |
Isolation |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates |
Suitable for safety functions | No |
Dimensions |
Width | 15 mm |
Height | 73 mm |
Depth | 58 mm |
Weights |
Weight, approx. | 28 g |
last modified: | 03/29/2019 |