6ES7350-2AH01-0AE0
FM350-2, Counter Mod., 8 Channels, 20KHz

From SIEMENS

SIMATIC S7-300, Counter module FM 350-2, 8 channels, 20 kHz, 24 V encoder for counting, frequency measurement, speed measurement, period duration measurement, dosing incl. configuration package and electronic documentation on CD-ROM
Supply voltage
Auxiliary voltage 1L+, load voltage 2L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from load voltage L+ (without load), max.150 mA
from backplane bus 5 V DC, max.100 mA
Encoder supply
Type of output voltageNAMUR-encoder supply: 8.2 V ±2 %
Short-circuit protectionYes
Output current
Rated value200 mA
Power loss
Power loss, typ.10 W
Digital inputs
Number of digital inputs8
Number of NAMUR inputs8
Functions1 each for gate start/ gate stop
Input voltage
for signal "0"-3 to +5V
for signal "1"11 to 30.2 V
Input current
for signal "0", max. (permissible quiescent current)2 mA
for signal "1", typ.9 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max.50 µs
Cable length
shielded, max.100 m
Digital outputs
Number of digital outputs8
Short-circuit protectionYes
Limitation of inductive shutdown voltage toL+ (-40 V)
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value0.5 A
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", max.300 µs
Switching frequency
with resistive load, max.500 Hz
with inductive load, max.0.5 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.4 A
— up to 60 °C, max.2 A
all other mounting positions
— up to 40 °C, max.2 A
Cable length
shielded, max.600 m
unshielded, max.100 m
Encoder
Connectable encoders
Incremental encoder (asymmetrical)Yes
24 V initiatorYes
24 V directional elementYes
NAMUR encoderYes
2-wire sensorYes
NAMUR encoder
Input signalto DIN 19 234
Input current for signal "0", max.1.2 mA
Input current for signal "1", min.2.1 mA
Input delay, max.50 µs
Input frequency, max.20 kHz
Cable length, shielded, max.100 m
Interrupts/diagnostics/status information
Diagnostics functionYes; Diagnostic information readable
Alarms
Diagnostic alarmYes; Parameterizable
Hardware interruptYes; Parameterizable
Diagnostics indication LED
Group error SF (red)Yes
Counter
Counter input 24 V
Number8; 32 bit or ±31 bit
Input voltage for signal "0"-3 to +5V
Input voltage for signal "1"11 to 30.2 V
Input current for signal "0", max. (permissible quiescent current)2 mA
Input current for signal "1", typ.9 mA
Input delay, max.50 µs
Counting frequency, max.20 kHz; Incremental encoder: 10 kHz
Cable length, max.100 m
Potential separation
Potential separation digital inputs
between the channels and backplane busYes; and shielding
Potential separation digital outputs
between the channels and backplane busYes; and shielding
Potential separation counter
between the channels and backplane busYes; and shielding
Connection method
required front connector1x 40-pin
Dimensions
Width80 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.460 g
last modified:03/29/2019